--	PNETMOD-MIB 1.02
--		History:
--	1.00	6. 11.2012 David Chvalkovsky - modified from NSD1800-MIB
--	1.01	9. 12.2015 Dusan Ferbas - comment compatibility
--	1.02	19. 10.2017 Vit Pekarek - Output Fuse description fixed
--
--  This is a MIB for Powernet module


PNETMOD-MIB DEFINITIONS ::= BEGIN
IMPORTS
	OBJECT-TYPE
		FROM RFC-1212
	Gauge, enterprises
		FROM RFC1155-SMI
	DisplayString, sysName
		FROM RFC1213-MIB;

--
-- Type Definitions
--

OnOff ::= INTEGER {
	off (0),
	on (1)
	}                              

OKFail ::= INTEGER {
	OK (0),
	Fail (1)
	}

ValueType ::= INTEGER {
	DI (1),
	AI (2)
	}
    
AlarmDescription ::= INTEGER {
	InputGridFailure (1),
	InputFuseFailure (2),
	PowerSourceFailure (3),
	PowerSourceCurrentOutOfRange (4),	
	BatteryVoltageOutOfRange (5),
	BatteryCurrentChargeOutOfRange (6),
	BatteryTemperatureOutOfRange (7),
	BatteryFuseFailure (8),
	OutputFuseFailure (9),
	OutputStateDisconnected (10)
	}
  
SignedNumber ::= INTEGER (-32758..32757)

Index ::= INTEGER (0..255)

TimeStamp ::= TimeTicks

--
-- Node Definitions
--

bke		OBJECT IDENTIFIER ::= { enterprises 27533 }

pnetMod	OBJECT IDENTIFIER ::= { bke 5 }

-- ---------------------------------------------------------- --
-- grid Group
-- ---------------------------------------------------------- --
grid	OBJECT IDENTIFIER ::= { pnetMod 1 }                                      

gridState OBJECT-TYPE
	SYNTAX	OKFail
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Grid State Ok/Fail value"
	::= { grid 1 }

gridFuse OBJECT-TYPE
	SYNTAX	OKFail
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Grid Fuse Ok/Fail value"
	::= { grid 2 }

-- ---------------------------------------------------------- --
-- source Group
-- ---------------------------------------------------------- --
powerSource	OBJECT IDENTIFIER ::= { pnetMod 2 }

powerSourceState OBJECT-TYPE
	SYNTAX	OKFail
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Power Source State Ok/Fail value"
	::= { powerSource 1 }

powerSourceCurrent OBJECT-TYPE
	SYNTAX	SignedNumber
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Power Source Current value XXXX divide by 10 to get XXX.X"
	::= { powerSource 2 }
  
-- ---------------------------------------------------------- --
-- accumulator Group
-- ---------------------------------------------------------- --
accumulator	OBJECT IDENTIFIER ::= { pnetMod 3 }

accuVoltage OBJECT-TYPE
	SYNTAX	SignedNumber
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Accumulator Voltage value XXXX divide by 10 to get XXX.X"
	::= { accumulator 1 }

accuCurrent OBJECT-TYPE
	SYNTAX	SignedNumber
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Accumulator Current value XXXX divide by 10 to get XXX.X"
	::= { accumulator 2 }

accuTemperature OBJECT-TYPE
	SYNTAX	SignedNumber
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Accumulator Temperature value -XXX divide by 10 to get -XX.X"
	::= { accumulator 3 }

accuFuse OBJECT-TYPE
	SYNTAX	OKFail
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Accumulator Fuse Ok/Fail value"
	::= { accumulator 4 }

-- ---------------------------------------------------------- --
-- output Group
-- ---------------------------------------------------------- --
output OBJECT IDENTIFIER ::= { pnetMod 4 }

outFuse OBJECT-TYPE
	SYNTAX	OKFail
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"Output Fuse Ok/Fail value"
	::= { output 1 }
  
outState OBJECT-TYPE
	SYNTAX	OnOff
	ACCESS	read-write
	STATUS	current
	DESCRIPTION
		"Output State On/Off value"
	::= { output 2 }

-- ---------------------------------------------------------- --
-- Alarm Group
-- ---------------------------------------------------------- --
alarms	OBJECT IDENTIFIER ::= { pnetMod 10 }

alarmTable OBJECT-TYPE
	SYNTAX	SEQUENCE OF AlarmEntry
	ACCESS	not-accessible
	STATUS	current
	DESCRIPTION
		"A list of input entries."
	::= { alarms 1 }

alarmEntry OBJECT-TYPE
	SYNTAX	AlarmEntry
	ACCESS	not-accessible
	STATUS	current
	DESCRIPTION
		"An entry containing information applicable
		to a particular input."
	INDEX { alarmIndex }
	::= { alarmTable 1 }

AlarmEntry ::= SEQUENCE {
  alarmIndex         Index,
  alarmDescription   AlarmDescription,
  valueType	         ValueType,
  value	             SignedNumber,
  alarmTimeStamp     TimeStamp
}

alarmIndex OBJECT-TYPE
	SYNTAX	Index
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"The input index."
	::= { alarmEntry 1 }

alarmDescription OBJECT-TYPE
	SYNTAX	AlarmDescription
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"The input alarm description."
	::= { alarmEntry 2 }

valueType OBJECT-TYPE
	SYNTAX	ValueType
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"The input digital or analog type."
	::= { alarmEntry 3 }
  
value OBJECT-TYPE
	SYNTAX	SignedNumber
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"The input alarm value."
	::= { alarmEntry 4 }
  
alarmTimeStamp OBJECT-TYPE
	SYNTAX	TimeStamp
	ACCESS	read-only
	STATUS	current
	DESCRIPTION
		"The input alarm duration."
	::= { alarmEntry 5 }

-- ---------------------------------------------------------- --
-- Trap Definitions
-- ---------------------------------------------------------- --
tsTrapAlarmStart TRAP-TYPE
	ENTERPRISE	pnetMod
	VARIABLES	{ sysName, alarmDescription, valueType, value }
	DESCRIPTION
		"This trap is sent each time an alarm is inserted
		into the alarm table."
	::= 1

tsTrapAlarmEnd TRAP-TYPE
	ENTERPRISE	pnetMod
	VARIABLES	{ sysName, alarmDescription, valueType, value }
	DESCRIPTION
		"This trap is sent each time an alarm is removed
		from the alarm table."
	::= 2

END